Datacom Systems D56 Průvodce řešením problémů Strana 67

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 104
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 66
67–
Programming Output Relaysand Powerline Carrier Devices
While in program mode, press
80 to enter Output Device Menu Mode. This
mode is used to program all output devices used in the system (4229 or 4204
Relay modules, or Powerline Carrier devices). Refer to the output device
table for
80 on the separate programming form when programming output
devices.
NOTE: If using Powerline Carrier Devices, the House ID of the devices must
be entered in data field
27.
After entering
80, the following prompts are displayed.
Output Device Displays
Enter Device No.
(00 = Quit) 01
Enter the Device Number 01 or 02 for a 4229, or 01, 02, 03, or 04 for a 4204,
or 01 – 08 for Powerline Carrier devices (or 00 to end these entries). Press
the [
] key to continue.
The [
] key is used to accept an entry and advance to the next prompt. The
[#] key is used to revert back to the last question to check or change an
entry. Press [
] to go forward again.
02 A EV ZL ZT
STT 0 0 0 00
This screen displays a summary of the current Device START programming
(for this example, device 02 has been selected).
Press the [
] key to continue.
02 A EV ZL ZT
STP – – 0 00
This screen displays a summary of the current Device STOP programming.
Press the [
] key to continue.
02 Device Action
No Response 0
Enter the desired device action as listed below. Press the [
] key to continue.
0 = No response 2 = Close and Stay Closed
1 = Close for 2 seconds 3 = Continuous Pulse on & off (1 sec ON, 1 sec OFF)
02 Start Event
Not Used 0
Enter the event to START the relay:
0 = Not used; 2 = Fault; 1 = Alarm; 3 = Trouble
A zone list must be used in conjunction with an event. If a zone type/system
operation is to be used instead of an event, enter 0.
Press the [
] key to continue.
02 Start: Zn List
No List 0
If a zone list will be used to START the relay action, enter the zone list
number (to be programmed in field
81): 1, 2, or 3. If not used, enter 0.
Press the [
] key to continue.
02 Start: Zn Typ
Not Used 00
If a zone type or system operation will be used to START the device action,
enter the appropriate two-digit code (see table that follows). If not, enter 00.
Press the [
] key to continue.
* Use 0 (Any) at
Disarming,.
CHOICES FOR ZONE TYPES
00 = Not Used 04 = Interior Follower 08 = 24 Hr Aux
01 = Entry/Exit #1 05 = Trouble Day/Alarm Night 09 = Fire
02 = Entry/Exit #2 06 = 24 Hr Silent 10 = Interior w/Delay
03 = Perimeter 07 = 24 Hr Audible 24 = Silent Burglary
CHOICES FOR SYSTEM OPERATION
20 = Arming-Home 36 = At Bell Timeout* 42 = System Battery Low
21 = Arming–Away 38 = Chime 43 = Communication Failure
22 = Disarming (Code + OFF) 39 = Any Fire Alarm 52 = Kissoff
31 = End of Exit Time 40 = Bypassing 58 = Duress
32 = Start of Entry Time 41 = AC Power Failure
33 = Any Burglary Alarm
Zobrazit stránku 66