–22–
Programming Wired Expansion Zones
Each zone must be programmed into the system using the
✱
56 Zone
Programming mode, which assigns characteristics that define the way the
system responds to faults on that zone. Refer to the Zone Response Type
section and the Zone Programming section for specific instructions on
programming wired expansion zones.
Check-Out Procedure For Wired Expansion Zones
Whenever it becomes necessary to disconnect power in order to add a module
or keypad, always disconnect the battery and then the AC transformer in that
order. After installation has been completed, connect the AC transformer first
followed by connection of the battery.
After you have completed installation and programming of all devices, all
expansion zones in the security system should be checked as follows:
1. Make certain that all devices and sensors connected to the wired
expansion zones are not in a faulted state. Doors and windows with
contacts should be closed, PIRs should be covered (use a cloth to mask
them temporarily if necessary).
2. With all zones intact (including hard-wired zones), the Alpha keypad
connected to the system should display :
* * S Y S T E M RE A D Y * *
If the following is displayed,
N O T RE A D Y - P r e s s
✱
t o sh o w f a u l t s
press the [
✱
] key to display the faulted zone(s). Restore any faulted
zone(s) as necessary (also make sure that you have connected a 1000 ohm
EOL resistor across the terminals of unused expansion zones on the 4219
or 4229 module).
When the **SYSTEM READY** message is displayed, you can proceed to
the next step.
3. Fault and restore every contact or sensor in each expansion zone
individually to ensure that it is being monitored by the system. Each time
a zone is faulted, the keypad should display the number of the faulted
zone. When each zone is restored, the **SYSTEM READY** message
should appear again.
You will need to observe the keypad in each zone as each zone is faulted
and restored.
4. When you get the proper displays on the keypad(s), the wired expansion
zones in the system are functioning properly.
If a "CHECK 09" message appears on the display, data from the control is not
reaching the zone expander module. Check the wiring and DIP switch settings.